| Contact resistance |
50 mฮฉ max. (Voltage drop method with 5 VDC 1 A) |
| Operating time |
25 ms max. (With rated operating power applied, 23 โ, not including contact bounce) |
| Reset time |
25 ms max. (With rated operating power applied, 23 โ, not including contact bounce) |
| Maximum operating frequency |
Mechanical: 18000 time/h
Rated load: 1800 time/h |
| Insulation resistance |
Between coil and contacts: 100 Mฮฉ min. (at 500 VDC)
Between contacts of same polarity: 100 Mฮฉ min. (at 500 VDC)
Between contacts of different polarity: 100 Mฮฉ min. (at 500 VDC) |
| Dielectric strength |
Between coil and contacts: 2000 VAC 50/60 Hz 1 min
Between contacts of same polarity: 1000 VAC 50/60 Hz 1 min
Between contacts of different polarity: 2000 VAC 50/60 Hz 1 min |
| Vibration resistance (destruction) |
10 to 55 to 10 Hz, 0.5-mm single amplitude (1-mm double amplitude) |
| Vibration resistance (Malfunction) |
10 to 55 to 10 Hz, 0.5-mm single amplitude (1-mm double amplitude) |
| Shock resistance (destruction) |
1000 m/s2 |
| Shock resistance (Malfunction) |
200 m/s2 |
| Endurance (Mechanical) |
100 million operations min. (switching frequency 18,000 operations/h) |
| Endurance (Electrical) |
200,000 operations min. (23 โ, switching frequency 1,800 operations/h) |
| Failure rate |
100 mA at 5 VDC (failure level: Preference value, Switching frequency: 120 operations per minute) |
| Ambient temperature (Operating) |
-25 to 40 โ (with no freezing or condensation) |
| Ambient humidity (Operating) |
5 to 85% RH |
| Weight |
Approx. 70 g |
| Mounting method |
Socket |